Tower
CX1K Series
- Capacity
- 1000 VA / 800 W
- Phase
- Single in, single out
- Battery
- 24 V DC standard, 36 V DC long run
- Dimensions
- 373 x 145 x 219 mm

Power protection
High frequency online, double conversion UPS: from 1 kVA tower units to modular frames up to 1200 kVA, for servers, telecom, medical and network equipment.





Online double conversion
Power is turned into DC and back into a clean sine wave, all the time. When the mains fails, the battery is already on the DC bus, so there is nothing to switch.
Mains onTransfer time 0 ms
Mains on: the rectifier feeds the inverter and charges the battery. The load runs on rebuilt power.
Product selector
Filter by form factor and power. Long run models, marked L, take external battery cabinets sized to the autonomy you need.

Tower

Tower

Tower

Tower

Tower

Rack mount

Rack mount

Three phase

Three phase

Outdoor cabinet

Outdoor cabinet

Modular
No series matches both filters. Clear one of them.
Specifications
| Parameter | Value |
|---|---|
| Capacity | 1000 VA / 800 W |
| Input voltage range | 110 to 300 V AC |
| Input frequency range | 46 to 54 Hz and 56 to 64 Hz |
| Input power factor | 0.98 |
| Output waveform | Pure sine wave |
| Output power factor | 0.8 |
| Efficiency | 81% line mode, 85% AC mode |
| Transfer time | 0 ms |
| Communications | RS232 and USB, SNMP optional |
| Operating temperature | 0 to 40°C |
Larger series follow the same architecture at higher ratings.
| Parameter | Value |
|---|---|
| Rated voltage | 380 / 400 / 415 V, 50 / 60 Hz |
| Input total harmonic distortion | Less than 3% |
| Efficiency | 0.99 at full load, 0.98 at half load |
| Architecture | Power modules in parallel, N plus X redundancy |
| Serviceability | Hot swap modules with self lock and full protection |
| Battery voltage window | 228 to 476 V DC, adjustable |
Power modules run in parallel and swap out live.

Typical critical loads
Network cabinets and shelters that ride through grid dips and generator changeover.
Server racks and data rooms on rack mount, three phase or modular frames.
Medical and laboratory equipment that needs a clean, unbroken supply.
Tills, card terminals and back office systems kept online through outages.
The wide input voltage and frequency window matters more in practice than the headline rating: it lets a unit ride an unstable supply and run cleanly from a generator, the normal condition on a remote site.
Management software supports Windows, Linux, macOS and major Unix systems, with remote control over SNMP across a local network or the internet.
We reply with a schedule, the datasheets and a delivery date from Riyadh stock.
Stock held in Riyadh · Freight, customs duty and clearance included